Versions
Temperature Controller with Alarm Function
Temperature Controller and Limiter with Alarm Function
Temperature Controller with Modbus communication
Temperature Controller / Limiter
Ex-TC
in Hazardous Areas
The eltherm electronic temperature controller Ex-TC has a wide control range of 0 °C up to + 450 °C and an ambient temperature range of - 40 °C up to + 50 °C. It has been developed for use in hazardous areas. Typical applications are frost protection and temperature maintenance. For different applications we offer different versions for wall mounting or for mounting on pipelines. You can choose between a temperature controller with alarm relay, with RS 485 interface with Modbus protocol or a temperature controller and limiter combination with alarm relay. The device can switch high rated currents and its round shape ensures optimum mechanical safety. The quick closing lid with snap lock is easy to use. All versions are suitable for our self-regulating heating cables (ELSR), as well as resistance heating cables (ELK, ELP).
Applications
Technical Benefits
- Three functional options
- No static charge
- Rapid closing of cover through snap fit, easy to use
- Optimum mechanical safety through round shape
- Modular design, compatible with Ex-it-R Junction Box and pipe mounting stand
- Easy setting and operation
Technical Data
| Enclosure | Polyamid, No static charge |
| Alarm limiter | 0 °C up to 450 °C, factory setting: 0 °C |
| Alarm controller | 0 °C up to 450 °C, factory setting: 5 °C |
| Measuring range | - 99 °C up to 450 °C (T1) |
| Operating / control voltage | 230 ±10 % V AC, 50/60 Hz |
| External fusing | 25 A (20 A) |
| Ex-suitable | |
| Weight | 1300 g to 1650 g |
| Terminal size | 0.2 - 4 mm² |
| Load relay | Single pole |
| Max. pipe temperature | 200 °C (Pipe mounting models) |
| Nominal Current | max. 25 A (up to 40 °C), max. 20 A (up to 50 °C) T6 with power cable ≥ 2.5 mm² |
| Relay output common alarm | 1 open contact 3 A, 250 VAC,100 VA or 5 A, 24 VDC, 100 W |
| Switching hysteresis | < 100 °C: 3 K, > 100 °C: 3 % |
| Switching point accuracy | < 2 K |
| IP rating | IP65 |
| Limiter restart threshold | 5 K below limiter threshold |
| Sensor connection controller / limiter | Ex-TC/A and Ex-TC/M: 1x intrinsically safe 3 wire connection with automatic length matching up to 20 Ω |
| Sensor connection controller / limiter | Ex-TC/AL: 2x intrinsically safe 3 wire connection with automatic length matching up to 20 Ω |
| Set point range | 0 °C up to 450 °C (T1) |
| Impact resistance | min. 7 J |
| Temperature units | °C or °F (°F on request) |
| Ambient temperature | - 20 °C up to + 50 °C (Pipe mounting models), - 40 °C up to + 50 °C (Wall mounting models) |
The eltherm designer