up to 260 °C
ELKM-AG-E
Fluoropolymer-insulated Heating Cable
This versatile heating cable is used for frost protection and temperature maintenance, even under highly corrosive environmental conditions. The heating cable ELKM-AG-E is suited and approved for use in hazardous areas. It is highly flexible permitting its use in many fields of application.
Compatible accessories:
Connection kit: Ex-Con 22/4 Si, Ex-Con 25/7, Ex-Con 36/4, ELVB-30, ELVB-30-1A
Junction Boxes: ELAK-Ex 2.00, ELAK-Ex 4.11, ELAK-Ex 4.12, ELAK-Ex 4.13, ELAK-Ex-R1, ELAK-Ex-R2, ELAK-2, ELAK-5, ELAK-5.1, ELAK-R1, ELAK-R2
Applications
Metallic and non-metallic materials, filter heating, hopper heating, heating hoods, automotive, paint shops
Technical Benefits
- High chemical and mechanical resistance
- Can be used in all industrial areas
- High operation temperature
- Easy to install, even on complex shapes
- Highly flexible
- Resistant to steam purging
- Moisture proof
Technical Data
| Bending radius, min. | 2.5 times the outer diameter |
| Ex-suitable | Yes |
| Heat conductor | twisted or coiled |
| Maximum maintain temperature | 260 °C |
| Output, max. | 30* W/m |
| Max. voltage | 750 V |
| Installation temperature, min. | - 60 °C |
| Impact resistance | 4 Joule |
| *Note | The power output per meter of heating cable and the maximum operating temperatures depend on the specific application. |