Versions

AO

BO

up to 140 °F

ELSR-MA

Low Temperature

eltherm‘s ELSR-MA self-regulating trace heater is extremely flexible and designed for installations which require smaller overall cable dimensions and shorter heating circuits. ELSR-MA is designed for freeze protection and all temperature maintain applications to 140 °F (60 °C).

  • Automotive
  • Pipelines
  • Valves, pumps
  • Vessels and tanks
Technical Benefits
  • Two nominal outputs 
  • Can be cut to length 
  • UV-resistant
  • Small dimensions 
  • Moisture proof

Product highlights

Click on the red and white markers for more details.

Bus wire:

Nickel plated copper

Self-regulating heating element

Insulation

Protective conductor:

Copper tin plated

Aluminum foil

Outer jacket:

TPE-O

  1. Bus wire:

    Nickel plated copper

  2. Self-regulating heating element
  3. Insulation
  4. Protective conductor:

    Copper tin plated

  5. Aluminum foil
  6. Outer jacket:

    TPE-O

Bus wire

Self-regulating heating element

Insulation

Protective braid:

Tinned copper

Outer jacket:

TPE-O

  1. Bus wire
  2. Self-regulating heating element
  3. Insulation
  4. Protective braid:

    Tinned copper

  5. Outer jacket:

    TPE-O

Technical Data

Minimum start up temperature
- 22 °F / - 30 °C
Maximum operating temperature, energized
140 °F / 60 °C
Maximum operating temperature, de-energized
140 °F / 60 °C
Nominal voltage (variable)
120 V AC / 240 V AC
Bending radius, min.
1 in / 25 mm
Installation temperature, min.
- 49 °F / - 45 °C

Downloads

Brochure Self-Regulating Trace Heaters, Letter Size, GB
pdf
7.5 MB
Declaration of conformity, DE, GB, FR
pdf
430.5 KB
Datenblatt ELSR-MA, DE
pdf
326.9 KB
Datasheet ELSR-MA, GB
pdf
326.2 KB
Accessories for ELSR, Letter Size, GB
pdf
356.0 KB
On the move globally
always within reach

Phone: +49 (0) 27 36 / 44 13-0

Fax: +49 (0) 27 36 / 44 13-50

E-mail: info@eltherm.com